10N203
Attic Fan Thermostat/Humidistat
Sensor, Remote Bulb
Remote Bulb Sensor, Differential 3 to 10 Between Switches each Switch is Fixed @ 3 Degrees Fahrenheit, Switch Action Two SPDT Switches Operating in Sequence, Right Switch Breaks R-B and makes R-W @ Setpoint on a Temperature Rise, Left Switch Breaks R-B and makes R-W if Temperature Continues to Rise thru Interstage Differential, Maximum 125 Degrees Fahrenheit, Range 0 to 100 Degrees Fahrenheit, Bulb Size 1/2 x 4 3/16 Inches, Capillary Length 20 Feet, Height 5 5/8 Inches, Width 2 Inches
Артикул:
3UC73
Каталог:
Grainger
Производитель:
HONEYWELL
Номер модели:
T678A1015
Страна производства:
Mexico
Вес (кг):
0.77
Спецификация:
Item: Line Voltage Thermostat |
Type: Remote bulb Temperature Control |
Switch Type: SPDT/SPDT |
Switch Action: switches operate in sequence, Right switch breaks R-B and makes R-W at setpoint on a temp rise, Left switch breaks R-B and makes R-W if temp continues to rise through interstage differential |
Number of Switches: 2 |
Control Range (F): 0 to 100 |
Differential (Deg. F): 3 to 10 |
Height (In.): 5-5/8 |
Width (In.): 2 |
Depth (In.): 2-5/8 |
Sensor Type: Copper Bulb |
Sensing Bulb Dia. (In.): 1/2 |
Sensing Bulb Length (In.): 4-3/16 |
Capillary Length (In.): 240 |
Characteristics: Two-stage, Controller without Bulb Holder, maximum connected load equals 2000VA |
For Use With: 2-Stage Heating or Cooling |
Color: Grey |
Application: 2-Stage Heating/Cooling |
Display: Analog |
Enclosure Type: Impact Resistant Norel |
Voltage Range: 120 to 277VAC |
Inductive Amps @ 120V: 8 |
Inductive Amps @ 240V: 5 |
Full Load Amps @ 120V: 8 |
Full Load Amps @ 240VAC: 5.1 |
Locked Rotor Amps @ 120V: 48 |
Locked Rotor Amps @ 240V: 30.6 |
Mounting: Any Position Outside the Sensing Area, 3 Slotted Holes In Back Of Case |
Number of Stages: 2 |
Agency Compliance: UL, E4436, Vol. 4, Sec. 11, Guide XAPX, CSA Listed: Report -1 |